Parametric changes are also required within the RSLogix 500 and Alarmware to synchronize the Modbus Drivers. Here are the steps:
1. Connect the MicroLogix to your PC using the required 1761-CBL cable
2. Launch RSLogix 500 Software
3. Set the Communications Driver to the Modbus RTU Slave and select the PLC data files
Next you need to setup communications for the Catalyst:
1. Launch the Alarmware for Cataylist 1.87
2. Connect the Catalyst to your PC
3. Modify the device settings in Alarmware. Once the window is open, select the “Modbus Port” tab and select the speed best suited for your application.
4. Modify the channel settings in Alarmware—channels one to 256 are available.
To finish integrating the system, you need to construct the Source Network Address (SNA). This comprises the Net/Node/Address. Net is either zero or one—zero is used for local physical I/O and one is used for remote PLC I/O—and node is the address of the PLC you wish to communicate. Lastly, the address points to the Modbus location mapped to the PLC.
Once the channels are configured, you are ready to assign them to your project.