Configuring a Physical Input Channel to read from a 4-20mA Transducer
How do I configure a physical input channel to read from a 4-20mA transducer?
- Once the SNA has been set for a Physical Input channel, you can click on the "Advanced" button.
- Set the "Scaling Option" to 4-20ma Scaling.
- The x1 and x2 values are set to 4ma and 20ma by default for the transducer.
- The y1 and y2 values must be configure properly to get a correct reading.
- Take a reading when the output of the transducer is 4ma. That will be the value for y1.
- Now take a reading when the output of the transducer is 20ma. That will be the value of y2.