Why have communications with my PLC failed ever since I upgraded from version 1.57?
Beginning at version 1.72, the CTS signal is driven ON and OFF to support RS485 connections.Some PLCs require that CTS be asserted continuously.
As of version 1.87, you will have the option of keeping CTS always ON when enabled.