Where can I find the Verbatim Gateway Autodialer PLC Connectivity Guide?
Where can I find the Verbatim Gateway Autodialer PLC Connectivity Guide?
Protocol | Connects Verbatim Gateway to: | Cable | Physical Layer Interface |
Pin Number | Cable End Gender |
Notes |
Allen-Bradley DH-485 | SLC500 Series Peer-to-Peer | Raco VAB-500-1 | DH-485 | 8 | Male | Connects directly to SLC DH-485 (RJ-45 Modular) Jack |
DH-485 Network via 1761-NET-AIC | A-B 1761-CBL-AS03 (3 meters) | DH-485 | Connects to 1761-NET-AIC (AIC+) Terminal Block Input |
|||
DH-485 Network via 1761-NET-AIC | A-B 1761-CBL-AS09 (9.5 meters) | DH-485 | Connects to AIC+ Terminal Block Input | |||
DH-485 Network via 1747-AIC | Raco VAB-500-1 | DH-485 | 8 | Male | Connects to DH-485 (RJ-45 Modular) Jack | |
Allen-Bradley DF-1 | SLC500 Series PLCs w/RS-232 Chan. 0 Port | Raco VAB-1 | RS-232 | 9 | Female | |
PLC-2 & PLC-3 via RS-232 | Raco VAB-1 | RS-232 | 9 | Female | ||
PLC-5 via Channel 0 Port | Raco VAB5-C0 | RS-232 | 25 | Male | ||
PLC-5 via 1785-KE | Raco VAB5-KE | RS-232 | 15 | Male | ||
PLC-5 via 1770-KF2 | Raco VAB5-KF2 | RS-232 | 25 | Female | ||
MicroLogix PLCs with RS-232 (Port 1) | Raco VAB-1 | RS-232 | 9 | Female | ||
Micrologix via Programming Port | Raco VMB-2 Plus A-B 1761-CBL-PM02 | RS-232 | 9 | Male | Raco cable mates to A-B cable for DF-1 Monitoring |
|
ControlLogix Logix 5500 w/RS-232 Port | Raco VAB-1 | RS-232 | 9 | Male | Straight connector shell does not allow Comm. port door to be closed. |
|
ControlLogix Logix 5500 w/RS-232 via Programmer Cable |
Raco VMB-2 Plus A-B 1756-CP3 | RS-232 | 9 | Male | RACO cable mates to A-B cable for DF-1 Monitoring |
|
Modbus (VB/GW is Master) | Modicon 984/584 PLC | Raco VMB-2 | RS-232 | 9 | Male | |
Modicon Micro PLC | Raco VMBM-1 | RS-232 | 9 | Male | ||
GE 9030/9070 via CCM | Raco VAB5-C0 | RS-232 | 25 | Male | Requires Model IC693CMM311/IC697CMM711 Co-processor |
|
Bristol-Babcock 3330/3350 | Raco VBB-1 | RS-232 | 15 | Male | ||
Bristol-Babcock 3335 | Raco VBB-2 (NEW) | RS-232 | 9 | Male | ||
Siemens TI-405 DCM PLCs | Raco VTI | RS-232 | 25 | Male | ||
A-B MicroLogix 1500 w/1764-LRP | Raco VAB-1 | RS-232 | 9 | Female | Must have 1764-LRP processor and Modbus Slave configured on its Port 1) |
|
Automation Direct Terminator I/O Modbus | Raco VAD-1 (NEW) | RS-232 | 15 | Male | ||
ProLinx Gateways | Raco VAB-1 | RS-232 | 9 | Female | ||
Modbus Plus | Modbus Plus Network, Bridges, Bridge Mux | User Supplied |