Verbatim Gateway - How do I disarm a single remote channel without disarming the entire alarm system?

How do I disarm a single remote channel without disarming the entire alarm system.  

Verbatim Gateway Owner's Manual

F.10.2 Remote Channel Alarm Criteria

 

4 5 ZZ

Function Read alarm criteria for channel ZZ

Response remote channel <ZZ> <criteria> or remote channel <ZZ> no

net address programmed

  • Note: By reading the channel alarm criteria first it will be easier to restore its original programming later.

 

4 5 ZZ 0

Function Disarms <ZZ> (i.e. eliminates all status reporting for the

channel). All other configuration information is preserved.

Response remote channel <ZZ> disarmed

 

Here are some possible choices when you are ready to rearm the input.

 

4 5 ZZ 1

Function Set channel number ZZ alarm criteria to normally 1.

Response remote channel <ZZ> normally 1

 

4 5 ZZ 2

Function Set channel number ZZ alarm criteria to normally 0.

Response remote channel <ZZ> normally 0

 

4 5 ZZ 3

Function Set channel number ZZ alarm criteria to no alarm. The channel

is still listed in all status reports.

Response no alarm condition for remote channel <ZZ>